Jasper Blanckenburg 66d9baba7a Go into discharge for 5s
The discharge circuit is only active while the SDC is open. If the SDC
never opens (or opens for a very short time only), but we go to
TS_INACTIVE, then the discharge circuit will never be active. Going into
a discharge state for 5s allows the PDU to open the SDC for long enough
to reach <60V.
2023-04-15 16:58:40 +02:00